Wacker Neuson Mobile Generators G50

Listing image Listing image Listing image
Specifications

Model G50 Year 2022 Sale Type New
Manufacturer Wacker Neuson Quantity 0 Manufacturer Qty 0
Price Contact for price CAD  
Description

G50 - Durable mobile generator offers reliable power

The G50 mobile generator offers the perfect power solution where single and three phase power are needed for construction commercial, industrial and special event applications. The sound-attenuated generator provide quiet operation and large fuel tank offers long run times, making it a flexible and reliable choice. A digital controller monitors and protects the generator and engine while providing continuous operating data on an easy to read LCD display.

  • Ideally suited for construction sites where durability, reliability and flexibility are required to supply continuous power for applications such as lighting, cranes, concrete mixers and conveyor belts.
  • Brushless, oversized alternators with separate excitation winding and AVR (Automatic Voltage Regulation) provide superior motor starting and enhanced ability to run non-linear loads.
  • Single switch start and simple, uncluttered control panel provide unmatched ease of use.
  • Automatic remote start capability standard which is ideal for temporary standby applications.
  • Fluid containment system, standard. Factory-installed customized options are available. These include, but are not limited to, cold weather options, fully equipped highway-ready trailers, and a camlock panel.
G50 TECHNICAL SPECIFICATIONS

Metric

  G50 (T4F) G50 (T4F) 600V

Dimensions 

L x W x H Operating (Skid) mm 2445 x 965 x 1346 2445 x 965 x 1346
L x W x H Shipping (Skid) mm 2540 x 1029 x 1654 2540 x 1029 x 1654
L x W x H Shipping/Operating (Trailer) mm 4064 x 1715 x 2032 4064 x 1715 x 2032

Weights 

Weight Dry (Skid) kg 1,262 1,262
Weight Operating (Skid) kg 1,536 1,536
Weight Shipping (Skid) kg 1,333 1,607
Weight Operating (Trailer) kg 1,936 1,936
Weight Shipping (Trailer) kg 1,661 1,661

Operating data 

Trailer coupling Type Pintle Pintle
Standby output   kW 42 42
Prime output  kW 38 38
Voltage 3 Phase V 240 / 480 240 / 480 / 600
Current 3 Phase (Prime) A 114 / 57 115 / 58 / 46
Current 1 Phase (Prime) A 120 / 240 120 / 240
Voltage 3 Phase V 208, 220, 240, 416, 440, 480 208, 220, 240, 416, 440, 480, 600
Voltage 1 Phase V 120, 127, 139, 240, 254, 277 120, 127, 139, 240, 254, 277, 346
Circuit breaker (Main) A 175 175
Frequency  Hz 60 60
Power factor 1 Phase cos Φ 1~ 1 1
Power factor 3 Phase cos Φ 3~ 0.8 0.8
Sound level (LwA) at Prime (23 ft / 7 m) dB(A) 67.7 67.7
Receptacles -20 Amp GFI Duplex 2 2
Receptacles -50 Amp Twist Lock 3 3

Engine / Motor 

Engine / Motor  Liquid-Cooled, 4 Cylinder Liquid-Cooled, 4 Cylinder
Engine / Motor manufacturer  Isuzu Isuzu
Emissions Certified Tier IV Tier IV
Displacement  cm³ 2,179 2,179
Operating performance SAE J1349 kW 49 49
Operating performance SAE J1995, ISO 8528-1 kW   44
at rpm  rpm 1,800 1,800
Coolant Capacity l 15.1 15.1
Engine oil Capacity l 10.4 10.4
Fuel type  #1/#2 ULSD Diesel
Fuel consumption (Prime Load) l/h 11.4 11.4
Tank capacity -Fuel l 318 318
Quantity (Battery) 1 1
Battery  V 12 12
Generator model  Mecc Alte, Brushless w/AVR Mecc Alte, Brushless w/AVR
Voltage control No Load to Full Load +/- % 1 1
Voltage control Steady State +/- % 0.2 0.2
Generator insulation (class)  H H
Frequency (Generator Speed) Hz 60 60
Runtime at 100% Prime Load h 24.3 24.3

Imperial
 

  G50 (T4F) G50 (T4F) 600V

Dimensions 

L x W x H Operating (Skid) in 96.25 x 38 x 53 96.25 x 38 x 53
L x W x H Shipping (Skid) in 100 x 40.5 x 65.1 100 x 40.5 x 65.1
L x W x H Shipping/Operating (Trailer) in 160 x 67.5 x 80 160 x 67.5 x 80

Weights 

Weight Dry (Skid) lb 2,783 2,783
Weight Operating (Skid) lb 3,388 3,388
Weight Shipping (Skid) lb 2,939 3,544
Weight Operating (Trailer) lb 4,268 4,268
Weight Shipping (Trailer) lb 3,663 3,663

Operating data 

Trailer coupling Type Pintle Pintle
Standby output   kW 42 42
Prime output  kW 38 38
Voltage 3 Phase V 240 / 480 240 / 480 / 600
Current 3 Phase (Prime) A 114 / 57 115 / 58 / 46
Current 1 Phase (Prime) A 120 / 240 120 / 240
Voltage 3 Phase V 208, 220, 240, 416, 440, 480 208, 220, 240, 416, 440, 480, 600
Voltage 1 Phase V 120, 127, 139, 240, 254, 277 120, 127, 139, 240, 254, 277, 346
Circuit breaker (Main) A 175 175
Frequency  Hz 60 60
Power factor 1 Phase cos Φ 1~ 1 1
Power factor 3 Phase cos Φ 3~ 0.8 0.8
Sound level (LwA) at Prime (23 ft / 7 m) dB(A) 67.7 67.7
Receptacles -20 Amp GFI Duplex 2 2
Receptacles -50 Amp Twist Lock 3 3

Engine / Motor 

Engine / Motor  Liquid-Cooled, 4 Cylinder Liquid-Cooled, 4 Cylinder
Engine / Motor manufacturer  Isuzu Isuzu
Emissions Certified Tier IV Tier IV
Displacement  in³ 133 133
Operating performance SAE J1349 hp 66 66
Operating performance SAE J1995, ISO 8528-1 hp   59
at rpm  rpm 1,800 1,800
Coolant Capacity US qt 16 16
Engine oil Capacity US qt 11 11
Fuel type  #1/#2 ULSD Diesel
Fuel consumption (Prime Load) US gal/h 3 3
Tank capacity -Fuel US gal 84 84
Quantity (Battery) 1 1
Battery  V 12 12
Generator model  Mecc Alte, Brushless w/AVR Mecc Alte, Brushless w/AVR
Voltage control No Load to Full Load +/- % 1 1
Voltage control Steady State +/- % 0.2 0.2
Generator insulation (class)  H H
Frequency (Generator Speed) Hz 60 60
Runtime at 100% Prime Load h 24.3 24.3